
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
6-1
6.1 Wiring
6 Commissioning
66000CommissioningCommissioning6-6.1Wiring6100Wiring6-
6.1.1 General wiring guidelines
General wiring guidelin es6-Verdrahtung_multi_Modul
The wiring is defined in the circuit diagram of the PNOZmulti Configura-
tor.
Note:
Information given in the "Technical details" must be followed.
Verdrahtung_Montageschiene mit Schutzerde verbinden
Always connect the mounting rail to the protective earth via an earth-
ing terminal. This will be used to dissipate hazardous voltages in the
case of a fault.
Verdrahtung_Netzteil_sichere_Trennung
The power supply must meet the regulations for extra low voltages
with safe separation.
Verdrahtung_multi_Achtung_Kabel_spannungsl_ziehen_Modul
Verdrahtung_multi_Feldbus_Hinweis Nutzerorg_CANopen
6.1.2 Connecting the supply voltage
Connecting the supply voltage6-Verdrahtung_multi_Feldbus_Versorgungsspannung_Mini
Connect the supply voltage to the fieldbus module:
Terminal 24 V: + 24 V DC
Terminal 0 V: 0 V
CAUTION!
Only connect and disconnect the expansion module when the
supply voltage is switched off.
NOTICE
When installing, you must refer to the guidelines published by
the CANopen User Group (CiA).
Komentáře k této Příručce