Pilz PNOZ s3 C 24VDC 2 n/o Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Senzory Pilz PNOZ s3 C 24VDC 2 n/o. Pilz PNOZ s3 C 24VDC 2 n/o User Manual [en] [de] [fr] [it] [es] Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - Safety relays

PNOZ s3Operating Manual-21395-EN-10Safety relays

Strany 2

PNOZ s3Operating Manual PNOZ s3 21395-EN-1010In1Fault Diagnostics: Power-up blocked due to short-term interruption at S12; input cir-cuits not operate

Strany 3 - Unit features

PNOZ s3Operating Manual PNOZ s3 21395-EN-1011Service life graphThe service life graphs indicate the number of cycles from which failures due to wear m

Strany 4 - Function description

PNOZ s3Operating Manual PNOZ s3 21395-EN-1012Technical DetailsGeneral 750103 751103Approvals CCC, CE, GOST, KOSHA, TÜV, cULus ListedCCC, CE, GOST, KOS

Strany 5 - Installation

PNOZ s3Operating Manual PNOZ s3 21395-EN-1013Relay outputs 750103 751103Max. short circuit current IK 1 kA 1 kAUtilisation categoryIn accordance with

Strany 6 - Preparing for operation

PNOZ s3Operating Manual PNOZ s3 21395-EN-1014Times 750103 751103Delay-on de-energisationWith E-STOP typ. 10 ms 10 msWith E-STOP max. 20 ms 20 msWith p

Strany 7

PNOZ s3Operating Manual PNOZ s3 21395-EN-1015Mechanical data 750103 751103Mounting position Any AnyMechanical life 10,000,000 cycles 10,000,000 cycles

Strany 8

PNOZ s3Operating Manual PNOZ s3 21395-EN-1016InformationA safety function's SIL/PL values are not identical to the SIL/PL values of the units tha

Strany 9

...Sachnummer Printed in Germany © Pilz GmbH & Co. KG, 2011+49 711 [email protected] GmbH & Co. KGFelix-Wankel-Straße 27

Strany 10 - Faults - malfunctions

PrefaceThis document is the original document.All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal

Strany 11 - Service life graph

PNOZ s3Operating Manual PNOZ s3 21395-EN-103PNOZ s3 safety relayThe safety relay provides a safety-related interruption of a safety circuit.The safety

Strany 12 - Technical Details

PNOZ s3Operating Manual PNOZ s3 21395-EN-104Safety featuresThe relay meets the following safety requirements:} The circuit is redundant with built-in

Strany 13 - 21395-EN-10

PNOZ s3Operating Manual PNOZ s3 21395-EN-105} Manual start: Unit is active once the input circuit is closed and then the start circuit is closed.} M

Strany 14

PNOZ s3Operating Manual PNOZ s3 21395-EN-106} Calculation of the max. cable length lmax in the input circuit:  Rlmax = max. overa

Strany 15

PNOZ s3Operating Manual PNOZ s3 21395-EN-107Connection} Supply voltageSupply voltage AC DC  } Input circuitInput circuit Single-channel Dual

Strany 16 - EC declaration of conformity

PNOZ s3Operating Manual PNOZ s3 21395-EN-108} Start circuit/feedback loopStart circuit/feedback loop Start circuit Feedback loopAutomatic start 

Strany 17 - Technical support

PNOZ s3Operating Manual PNOZ s3 21395-EN-109Status indicators Power Supply voltage is present. In1 Input circuit at S12 is closed. In2 Input circui

Příbuzné modely PNOZ s3 24VDC 2 n/o

Komentáře k této Příručce

Žádné komentáře