Pilz PSS67 F 16DI SB-T Uživatelský manuál Strana 29

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 51
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 28
Operating Manual: PSS67 F 16DI SB-T 7-3
Digital inputs
Features:
16 digital inputs I
0
... I
15
The inputs are connected using 8 5-pin M12 plug-in connectors. Two
inputs are available on each M12 plug-in connector.
Only input signals that operate in accordance with the failsafe principle
(on switching off) are permitted for safety-related applications.
Signals may be connected using unshielded cables.
Test pulse outputs
Features:
4 test pulse outputs T
0
to T
3
The assignment of test pulses to inputs is permanently specified and
cannot be configured using the system software’s configurator.
Test pulses cannot be addressed via the PSS process I/O-image.
Test pulses must only be used for test signals.
Identical test pulses within a test pulse group (see Fig. 7.4) can take a
maximum 250 mA load. If you use all the test pulses, the maximum
permitted current load per plug-in connector and test pulse is 125 mA.
Zobrazit stránku 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 50 51

Komentáře k této Příručce

Žádné komentáře