Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
6-5
6.2 Terminal configuration
6 Wiring
Screw terminals:
PSSu BP 1/12S
PSSu BP 1/12S-T
Cage clamp terminals:
PSSu BP 1/12C
PSSu BP 1/12C-T
Without C-rail:
11: Output Tx (send data)
21: Input Rx (receive data)
12-22: GND
(12-22-15-25 linked within the base
module)
13-23: Cable shield
(13-23-16-26 linked within the base
module)
14: Output RTS
24: Input CTS
15-25: GND
(12-22-15-25 linked within the base
module)
16-26: Cable shield
(13-23-16-26 linked within the base
module)
Screw terminals:
PSSu BP-C 1/12S
PSSu BP-C 1/12S-T
Cage clamp terminals:
PSSu BP-C 1/12C
PSSu BP-C 1/12C-T
With C-rail:
11: Output Tx (send data)
21: Input Rx (receive data)
12-22: GND
(12-22 linked within the base module)
13-23: C-rail supply,
shield connection
(13-23 linked within the base module)
14: Output RTS
24: Input CTS
15-25: GND
(12-22-15-25 linked within the base
module)
16-26: C-rail supply,
cable shield
(13-23-16-26 linked within the base
module)
Base module Terminal configuration