PROFIBUS-DP-Slave Operating Manual 7-1
Appendix
Example
Data block DB 050 is selected for setting the parameters. The data block
is configured in OB 020. The configuration corresponds to Example 5 in
Chapter 4. SB 230 is called up in OB 001.
OB 020 Cold start ST
:A DB 004 ;Registered hardware on standard section
:L KH B220 ;Enter the code of the module (B220)
:T DW 0027 ;on slot 7
:
:A DB 005 ;Start address for Slave module
:L KH 0000 ;Start address (Offset) is 0
:T DW 0007 ;Slave module on slot 7
:
:L KH 0000 ;Reset the used flag
:T MB 000.00 ;in OB 001
:T MW 030.00 ;
:T MW 010.00 ;
:
:A DB 050 ;Data block for setting the parameters
;(input parameter “DB” from SB 230)
:L KH 2500 ;ID-Number
:T DW 0258 ;
:
:L KH 0004 ;Length of the diagnostic data [Bytes]
:T DW 0259 ;
:
:L KH C1C0 ;Configuration data
:T DW 0384 ;
:L KH 00C0 ;
:T DW 0385 ;
:L KF 0010 ;Reserved
:T DW 0783 ;
:L KH 00F5 ;Reserved
:T DW 0795 ;
:
:L KF 0001 ;Station address [0-126]
:T DW 0800 ;