PNOZ s2
Operating Manual PNOZ s2
21394-EN-07
4
Safety features
The relay meets the following safety requirements:
} The circuit is redundant with built-in self-monitoring.
} The safety function remains effective in the case of a component failure.
} The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
} The unit has an electronic fuse.
Block diagram/terminal configuration
Input
A1 A2
Power
Reset/
Start
S34
Y32
K1
K2
13
23 33 41
24 34 42
14
Interface
expansion
unit
Centre: Front view with cover, right: Front view without cover
*Safe separation in accordance with EN 60947-1, 6 kV
Function description
} Single-channel operation: no redundancy in the input circuit, earth faults in the reset
and input circuit are detected.
}
Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit is closed and then the start circuit is
closed.
}
Monitored start with falling edge: Unit is active once
the input circuit is closed and then the start circuit is closed and opened again.
the start circuit is closed and then opened again once the input circuit is closed.
}
Monitored start with rising edge: Unit is active once the input circuit is closed and
once the start circuit is closed after the waiting period has elapsed (see technical de-
tails).
} Increase in the number of available instantaneous safety contacts by connecting con-
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.